APC DX Manual de servicio

Busca en linea o descarga Manual de servicio para Acondicionadores de aire del sistema de división APC DX. APC DX Technical data Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 62
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
®
TM
Computer Room Air-Conditioning—60 Hz
Technical Data
Vista de pagina 0
1 2 3 4 5 6 ... 61 62

Indice de contenidos

Pagina 1 - Technical Data

®TMComputer Room Air-Conditioning—60 HzTechnical Data

Pagina 2

6APC NetworkAIR™ FM-DXStandard FeaturesDouble Skin PanelsThe frame is bolt together 12 gauge formed steel for maximum strength. Cabinet is serviceabl

Pagina 3 - Contents

Standard FeaturesAPC NetworkAIR™ FM-DX 7Steam Generating HumidifierThe humidifier utilizes a pure steam generator specifically designed for precision

Pagina 4

8APC NetworkAIR™ FM-DXOptional FeaturesBrazed Plate CondenserWater- and Glycol-cooled systems employ a brazed plate heat exchanger. The condenser is

Pagina 5 - Overview

Optional FeaturesAPC NetworkAIR™ FM-DX 9Additional Programmable Input/Output Interface ModulesEach system is equipped with up to 3 additional discret

Pagina 6 - 2APC NetworkAIR™ FM-DX

10 APC NetworkAIR™ FM-DXMicroprocessor ControllerMicroprocessor Controller The microprocessor controller is standard on each system. The con-troller

Pagina 7 - APC NetworkAIR™ FM-DX 3

APC NetworkAIR™ FM-DX 11Upflow modelsFM Upflow componentsMotor and fan assemblyElectrical junction boxSteam headUser interface boxDX coilFirest

Pagina 8 - 4APC NetworkAIR™ FM-DX

12 APC NetworkAIR™ FM-DXDownflow modelsFM Downflow componentsAir filtersHumidifier (optional)Economizer coil (optional)Condensate pump (optional)

Pagina 9

APC NetworkAIR™ FM-DX 13Performance Specifications—Air CooledNET COOLING MODE CAPACITY - BTU/HR* FM 35 FM 5080F DB, 67F WB (26.7C DB, 19.4C WB) 50% R

Pagina 10 - Standard Features

Performance Specifications—Air Cooled14 APC NetworkAIR™ FM-DXPerformance Specifications - Air CooledFM-DX FM 35 FM 50AIR SYSTEM -- DIRECT DRIVE CENT

Pagina 11 - APC NetworkAIR™ FM-DX 7

APC NetworkAIR™ FM-DX 15Performance Specifications—Water CooledNET COOLING CAPACITY - BTU/HR* FM 35 FM 5080F DB, 67F WB (26.7C DB, 19.4C WB) 50% RHTo

Pagina 13 - APC NetworkAIR™ FM-DX 9

Performance Specifications—Water Cooled16 APC NetworkAIR™ FM-DXPerformance Specifications—Water CooledFM-DX FM 35 FM 50ECONOMIZER -- NET COOLING CAPA

Pagina 14 - Microprocessor Controller

APC NetworkAIR™ FM-DX 17Performance Specifications—Glycol CooledNET COOLING CAPACITY - BTU/HR* FM 35 FM 5080F DB, 67F WB (26.7C DB, 19.4C WB) 50% RHT

Pagina 15 - Upflow models

Performance Specifications—Glycol Cooled18 APC NetworkAIR™ FM-DXPerformance Specifications—Glycol CooledFM-DX FM 35 FM 50ECONOMIZER -- NET COOLING CA

Pagina 16 - Downflow models

APC NetworkAIR™ FM-DX 19Electrical DataAIR COOLEDREHEAT ElectricHUMIDIFIER Electrode Canister - SteamVOLTAGE 208 230 480 600FM 35OA-w/DX 59.7 58.4 27

Pagina 18 - 14 APC NetworkAIR™ FM-DX

APC NetworkAIR™ FM-DX 21Dimensional DataFM Downflow* All dimensions are in inches (mm).na0214a16.14 (410)8.66 (220) 15.75 (400)11.81 (300)18.07 (459)

Pagina 19 - APC NetworkAIR™ FM-DX 15

Dimensional Data22 APC NetworkAIR™ FM-DXFM Upflow* All dimensions are in inches (mm).FM upflow, rear-returnna0329a

Pagina 20 - 16 APC NetworkAIR™ FM-DX

Dimensional DataAPC NetworkAIR™ FM-DX 23

Pagina 21 - APC NetworkAIR™ FM-DX 17

Dimensional Data24 APC NetworkAIR™ FM-DXFM FloorstandFM Sub-BaseOrderable Floorstand HeightRange12” (FM35) Adjustable 10.5”-13.5”15” (FM35) Adjustabl

Pagina 22 - 18 APC NetworkAIR™ FM-DX

Dimensional DataAPC NetworkAIR™ FM-DX 25FM 20” Upflow PlenumFM 24” Upflow Plenum

Pagina 23 - Electrical Data

ContentsAPC NetworkAIR™ FM-DX iOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 24

Dimensional Data26 APC NetworkAIR™ FM-DXFM35 12” Downflow PlenumFM50 18” Downflow Plenumna0717a

Pagina 25 - Dimensional Data

APC NetworkAIR™ FM-DX 27Air-Cooled CondensersAir-cooled condenser—performance/electrical dataOHE SKU VoltageAmbient TemperatureAir Quantity Fan/Motor

Pagina 26 - FM upflow, rear-return

Air-Cooled Condensers28 APC NetworkAIR™ FM-DX2-fan air-cooled condenser3-fan air-cooled condenserAPC PART CIRCUIT VOLTAGEACCD75028 single 208-230/1/6

Pagina 27

Air-Cooled CondensersAPC NetworkAIR™ FM-DX 29 2-fan air-cooled condenser4-fan air-cooled condenserAPC PART CIRCUIT VOLTAGEACCD75040 single 208-230/3/

Pagina 28 - FM Sub-Base

Air-Cooled Condensers30 APC NetworkAIR™ FM-DX2-fan low-noise condenser3-fan low-noise condenserAPC PART CIRCUIT VOLTAGEACCD75055 single 208-230/3/60A

Pagina 29 - FM 24” Upflow Plenum

Air-Cooled CondensersAPC NetworkAIR™ FM-DX 314-fan low-noise condenser5-fan low-noise condenserAPC PART CIRCUIT VOLTAGEACCD75070 single 208-230/3/60A

Pagina 30 - FM50 18” Downflow Plenum

32 APC NetworkAIR™ FM-DXFluid Coolers*Fluid coolers can be selected for multiple indoor air conditioning units from the factory. Consult factory for

Pagina 31 - Air-Cooled Condensers

Fluid CoolersAPC NetworkAIR™ FM-DX 333-fan fluid cooler2-fan fluid coolerAPC PART VOLTAGEACFC75126 208-230/1/60ACFC75198 208-230/3/60ACFC75199 480/3/

Pagina 32 - 3-fan air-cooled condenser

Fluid Coolers34 APC NetworkAIR™ FM-DX3-fan fluid cooler4-fan fluid coolerAPC PART VOLTAGEACFC75202 208-230/3/60ACFC75203 480/3/60ACFC75143 600/3/60AP

Pagina 33 - 4-fan air-cooled condenser

Fluid CoolersAPC NetworkAIR™ FM-DX 353-fan low-noise fluid cooler4-fan low-noise fluid cooler APC PART VOLTAGEACFC75158 208-230/3/60ACFC75159 480/3/6

Pagina 34 - 3-fan low-noise condenser

ii APC NetworkAIR™ FM-DX

Pagina 36 - Fluid Coolers

APC NetworkAIR™ FM-DX 37Pump SpecificationsPump performancePump connection sizesPump electrical dataHP (kW) 3/4 (.56) 1 (.75) 1.5 (1.1) 2 (1.5)LINE

Pagina 37 - 2-fan fluid cooler

Pump Specifications38 APC NetworkAIR™ FM-DXFM Single Pump PackageFM Dual Pump Package

Pagina 38 - 4-fan fluid cooler

APC NetworkAIR™ FM-DX 39Piping Connections*Dimensions are shown in inches (millimeters)Air outlets (downflow only)Main powerWater/glycol out or ho

Pagina 39 - 4-fan low-noise fluid cooler

40 APC NetworkAIR™ FM-DXElectrical ConnectionsUpflow ModuleController boardDownflow ModuleDIP switchesMain circuit breakerDB-9 connector/RS232

Pagina 40

APC NetworkAIR™ FM-DX 41Guide SpecificationsPART 1 — PART 1 GENERAL1.01 SUMMARYA. The environmental control system shall be designed specifically for

Pagina 41 - Pump Specifications

Guide Specifications42 APC NetworkAIR™ FM-DXPART 2 — PART 2 PRODUCT2.01 STANDARD COMPONENTSA. CABINET CONSTRUCTION1. Double Skin Panels:Exterior pane

Pagina 42 - FM Dual Pump Package

Guide SpecificationsAPC NetworkAIR™ FM-DX 43D. MASTER CONTROLLER1. Monitoring and Configuration: The master display shall allow monitoring and config

Pagina 43 - Piping Connections

Guide Specifications44 APC NetworkAIR™ FM-DXE. ELECTRICAL PANEL1. The control voltage shall be 24 VAC, class 2 circuit. The electrical panel shall co

Pagina 44 - Electrical Connections

Guide SpecificationsAPC NetworkAIR™ FM-DX 45L. EVAPORATOR FREEZE PROTECTION1. Suction pressure shall be actively monitored and controlled to eliminat

Pagina 45 - Guide Specifications

APC NetworkAIR™ FM-DX 1OverviewThe modular, Floor Mount com-puter room air-conditioning system offers efficient, effective and eco-nomical cooling fo

Pagina 46

Guide Specifications46 APC NetworkAIR™ FM-DX2.02 OPTIONAL COMPONENTSA. BRAZED PLATE CONDENSER1. Water and glycol cooled systems shall employ a brazed

Pagina 47

Guide SpecificationsAPC NetworkAIR™ FM-DX 47G. CABLE WATER DETECTOR1. A leak detection sensing cable shall be shipped loose with the unit. If water o

Pagina 48

Guide Specifications48 APC NetworkAIR™ FM-DXN. ENVIRONMENTAL MONITORING AND MANAGEMENT1. Environmental Monitoring Unit: A stand-alone unit shall perf

Pagina 49

Guide SpecificationsAPC NetworkAIR™ FM-DX 49PART 3 — PART 3 INDIVIDUAL SYSTEMS3.01 AIR-COOLEDA. The indoor unit shall consist of an evaporator sectio

Pagina 50

Guide Specifications50 APC NetworkAIR™ FM-DXB. FLUID COOLER1. Outdoor Fluid Cooler: The fluid cooler casing shall be of aluminum, and all structural

Pagina 51

Guide SpecificationsAPC NetworkAIR™ FM-DX 513.05 MULTICOOLA. Air, Water and Glycol systems shall have the option of a chilled water coil that is desi

Pagina 53

APC NetworkAIR™ FM-DX 53Guidelines for InstallationThe NetworkAIR FM provides reliable, accurate temperature and humidity control of computer rooms,

Pagina 54

Guidelines for Installation54 APC NetworkAIR™ FM-DXReceiving the unit Your NetworkAIR FM unit has been completely tested and inspected prior to shipm

Pagina 55

Guidelines for InstallationAPC NetworkAIR™ FM-DX 55Water supply to humidifier 1. The humidifier fill valve orifice is sized for supply water pressure

Pagina 56

2APC NetworkAIR™ FM-DXScalable Solution for Critical EnvironmentsTemperature and Humidity Design ConditionsMaintenance of temperature and humidity de

Pagina 59

APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following ways:• Visit the AP

Pagina 60

Scalable Solution for Critical EnvironmentsAPC NetworkAIR™ FM-DX 3Dedicated Dehumidification CycleA dedicated dehumidification cycle allows the syste

Pagina 61

Scalable Solution for Critical Environments4APC NetworkAIR™ FM-DXHumidity ControlIncreasing heat densities in data centers are leading to more hot sp

Pagina 62 - 990-1100D 08/2005

Scalable Solution for Critical EnvironmentsAPC NetworkAIR™ FM-DX 5Glycol-Cooled ConfigurationGlycol-cooled systems are completely charged and factory

Comentarios a estos manuales

Sin comentarios