APC Automatic Disconnect Switch Manual de usuario Pagina 13

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 12
1-5
Figure 1-2. UTS Power Connectors
Generator Inlet This is the male L14-20 or L14-30 connector for the power input cable that
connects from the generator, and is supplied by the customer. Additional
generator power input cable information is provided in Appendix A of the Site
Preparation and Installation Guide (990-2992A).
UPS Inlet This is the female IEC 320 connector for the power input cable from the
uninterruptible power supply (UPS).
Convenience Outlet This is a standard female NEMA 5-15, 120 Volt convenience outlet for
powering a UPS, or other device. It derives its power from the utility, or the
generator input.