USER’S GUIDE
AUTOMATIC TRANSFER SWITCH
177
SNMP problems
Problem Solution
Unable to perform a GET • Verify the read (GET) community name.
Use the control console or Web interface to ensure that
the NMS has access. See
SNMP.
Unable to perform a SET • Verify the read/write (SET) community name.
Use the control console or Web interface to ensure that
the NMS has write (SET) access. See
SNMP.
Unable to receive traps at
the NMS
Query the mconfigTrapReceiverTable PowerNet MIB
OID to check whether the NMS IP address is listed
correctly and whether the community name defined for
the NMS matches the community name in the table. Use
SETs to the mconfigTrapReceiverTable OIDs, or use
the control console or Web interface to make any
necessary corrections. See
SNMP.
Traps received at an NMS
are not identified
See your NMS documentation to verify that the traps are
properly integrated in the alarm/trap database.