B. Regulatory Requirements: Comply with applicable requirements of the laws, codes, ordinances,
and regulations of Federal, State, and local authorities having jurisdiction. Obtain necessary
approvals from such authorities.
1. Where applicable, the UPS shall also be designed in accordance with publications from the
following organizations and committees:
a. National Fire Protection Association (NFPA).
b. National Electrical Manufacturers Association (NEMA).
c. Occupational Safety and Health Administration (OSHA).
d. Institute of Electrical and Electronics Engineers, Inc. (IEEE); ANSI/IEEE 519.
e. ISO 9001
f. ISO 14001
C. Pre-Installation Conference: Conduct pre-installation conference in accordance with
[Section 01 31 19 - PROJECT MEETINGS] [Section 01200 - PROJECT MEETINGS]. Prior to
commencing the installation, meet at the Project site to review the material selections, installation
procedures, and coordination with other trades. Pre-installation conference shall include, but shall
not be limited to, the Contractor, the Installer, and any trade that requires coordination with the work.
Date and time of the pre-installation conference shall be acceptable to the Owner and the
Architect/Engineer.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Deliver materials to the Project site in supplier’s or manufacturer’s original wrappings and
containers, labeled with supplier’s or manufacturer’s name, material or product brand name, and lot
number, if any.
B. Store materials in their original, undamaged packages and containers, inside a well-ventilated area
protected from weather, moisture, soiling, extreme temperatures, and humidity.
1.8 PROJECT CONDITIONS
A. Environmental Requirements: Do not install solid state UPS until space is enclosed and
weatherproof, wet work in space is completed and nominally dry, work above ceilings is complete,
and ambient temperature and humidity conditions are and will be continuously maintained at values
near those indicated for final occupancy.
1. The UPS shall be capable of withstanding any combination of the following environmental
conditions in which it must operate without mechanical or electrical damage, or degradation of
operating characteristics.
a. Storage Ambient Temperature: -22 °F (-30 °C) to 158 °F (70 °C) without internal battery;
5 °F (-15 °C) to 113 °F (45 °C) with internal batteries.
b. Operating Ambient Temperature: 32 °F (0 °C) to 104 °F (40 °C) (77 °F [25 °C] is ideal
for most battery types).
c. Relative Humidity: 0 percent to 95 percent non-condensing.
d. Altitude: Maximum installation with no derating of the UPS output shall be 3281 feet
(1000 meters) above sea level.
e. Audible Noise: The UPS shall not produce audible noise at a distance of 39 inches
(1 meter) in excess of the following:
1) 10 kVA to 15 kVA: 51 dBA.
2) 20 kVA to 30 kVA: 55 dBA.
1.9 WARRANTY
A. General: See [Section 01 77 00 - CLOSEOUT PROCEDURES] [Section 01770 - CLOSEOUT
PROCEDURES].
B. Special Warranty: The Contractor shall warrant the work of this Section to be in accordance with
the Contract Documents and free from faults and defects in materials and workmanship for period