15NetShelter SV User Manual
Installation
1. Use the Torx T30/#2 Phillips wrench (provided) to adjust a vertical mounting flange. Remove the
T30 screws at the top, middle, and bottom of the vertical mounting flange. Save the screws for
adjustment and reinstallation in the new position.
CAUTION
STABILITY HAZARD
When adjusting vertical mounting flanges, ensure that no equipment is installed on the
vertical mounting flanges.
Failure to follow these instructions can result in injury or equipment damage.
NOTICE
• Vertical mounting flange attachment positions are in 10 mm (0.4 in) increments.
• If the vertical mounting flanges are adjusted from their factory mounting position more
than 60 mm (2.4 in), the vertical mounting flanges attach to the cabinet side brace using
cage nuts and fasteners.
ns2014a
600 mm cabinet
800 mm cabinet
ns2030a
Vista de pagina 20