Environmental Monitoring Card 7
Sensor Zone Connections
Connection
information
The Environmental Monitoring Card supports normally open
and normally closed loop systems, and allows mixing of
normally open and normally closed sensors on any zone. Do
not cross-connect the card’s sensors with sensors from any
other system.
Multiple sensors
in a zone
To use more than one sensor on a zone, connect normally open
sensors in parallel and normally closed sensors in series. To
avoid receiving alarm indications on unused zones, install a
jumper wire between the COM and NC connectors for each
unused zone.
Normally Open Zone
GND/NO
COM
NC
Normally Closed Zone
GND/NO
COM
NC
Combined Normally Open
and Normally Closed Zone
GND/NO COM
NC
Normally Open Zone
GND/NO
COM
NC
Normally Closed Zone
GND/NO
COM
NC