InRow Air Cooled RD Installation18
Joining the Equipment to Enclosures
Joining to SX enclosures
The equipment comes with four joining brackets (two for the front and two for the rear).
1. Remove the front and rear
doors. See “Door removal” on
page 14.
2. Locate the four joining
brackets. Rotate each bracket
ninety degrees toward the
adjoining enclosure so the
bracket is parallel to the floor
and install using the screws
provided with the enclosure.
For more information, see
the Unpacking, Installation, and Customization manual for the NetShelter
®
SX Enclosure.
Joining to VX and VS enclosures
For information on joining the equipment to VX and VS enclosures, see the installation sheet
NetShelter
®
SX or VS External Joining Kit—AR7601, AR7602.