APC AP9617 Manual de usuario Pagina 61

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 104
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 60
®
USER’S GUIDE
network management card
59
8- Amp Hours (AHr) The battery amp-hour size, in amp-hours.
9- Compensation Method On enables and
Off disables battery temperature
compensation.
10- Comp Temp Coefficient
(mV/degC/cell)
The compensation temperature coefficient, in millivolts.
Minimum: – 4.99
Maximum: 0
11- High Knee Temperature
(mV/degC/cell)
The temperature (in Celsius) above which Float Voltage
no longer changes to compensate for increase in
temperature.
Minimum: 0
Maximum: 100.00
12- Low Knee Temperature
(mV/degC/cell)
The temperature (in Celsius) below which Float Voltage
no longer changes to compensate for decrease in
temperature.
Minimum: – 100.00
Maximum: 100.00
13- Accept Changes Use this option to save your changes.