APC PD40G6FK1-M Manual de instrucciones Pagina 11

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 16
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 10
7InfraStruXure Power Distribution Unit 40kW Instructions for Electricians
Install a circuit breaker
Warning: When you connect the InfraStruXure PDU to utility power, you must install a
circuit breaker to protect the PDU against over-current.
Determine the amperage of the circuit breaker that you need to install:
Route the input conductors to the Main Input switch
For overhead wiring, run the input conductors directly to the Main Input switch.
For wiring under a raised floor, run the input conductors through the wireway (
)
within the PDU to the Main Input switch.
Input Voltage Circuit Breaker Amperage
208V 175A
480V 80A
600V 60A