990-1467C InfraStruXure System – Service Manual – Installation and Start-Up 13
Emergency Power Off (EPO)
Overview
To provide a mechanism for emergency power off, attach a remote switch (not included) to the EPO
interface on the PDU monitoring unit. The EPO interface () is connected to the PDU Main Input switch
() and to the UPS internal EPO switch (). (Control wires from the PDU to the UPS are connected
during installation of the InfraStruXure system.)
When the EPO is activated, the main input circuit breaker to the PDU transformer is opened, the UPS DC
Disconnect breaker is opened, and the UPS System Enable switch is turned off. In this sequence, there is
not power from the PDU transformer and there is no power from the UPS inverters and batteries.
Note: APC offers an optional InfraStruXure EPO System (EPW9). Contact your APC sales
representative, or visit the APC Web site (www.apc.com) for more information.
See “Connect an Emergency Power Off Switch” on page 33 for instructions on how to connect
an EPO switch to the PDU.
PDU
Switch
UPS
psx0018a