15NetBotz Rack Monitor 450/550/570 Installation and Quick Configuration Manual
Root account user ID and password
Your NetBotz appliance has a pre-configured root account. The root account is used only for appliance
communications that are performed using the USB Console Port, e.g., when you use the Serial
Configuration Utility to specify network settings. The default User ID and Password for this account are:
User ID: root
Password: apc
Note: You cannot change the root account User ID. To increase security, use the
Advanced View Change Root Password Tool to change the default root account
password.
Lost password recovery
To recover from a lost password:
1. Locate the reset switch on the rear of the appliance, to the right of the AC Line Inlet port.
2. Use a thin wire such as a paper clip to press the reset switch for 10 seconds. This causes the
system to restart.
3. Once the system restarts, log in within two minutes using the default login values:
For Advanced View:
User ID: apc
Password: apc
For the console:
User ID: root
Password: apc
Note: If you do not log in within two minutes after holding down the reset switch,
you must repeat the procedure.
4. After you log in, change the password to increase security.
Basic View
Use the Basic View to view the current sensor data, image capture, and other appliance data in an
HTML-based interface. Use the Basic View to perform basic appliance configuration. The configuration
tasks available from the Basic View are limited and are included for initial appliance installation and
setup. This view is provided to allow you to use a Web browser to view appliance status.
For a list of supported Web browsers and versions, see the release notes available on the Utilty CD.
Advanced View
Use the Advanced View to view sensor data, camera images, and other appliance data in a custom Java
application. You can also use the Advanced View to generate relay output actions and configure all
appliance features. The Advanced View is a stand-alone application that must be installed on a supported
network-attached computer.
For more information on the Basic View or the Advanced View, see the NetBotz Appliance
Users Guide.