InRow Half-Rack RC Installation18
Condensate pump drain connection.
Condensate pump drain installation.
The condensate drain line is
coiled inside the equipment, allowing you to route the condensate
drain line for either top or bottom use. See the table “Piping and
electrical access locations” on page 11 for more information. Use the
provided grommets to properly secure and protect the condensate
drain line.
Chiller
There are three types of chillers to which the equipment can be
connected:
• APC size-matched chiller/thermal storage system
• Building chilled water system
• Existing dedicated chiller
See the chiller manufacturer’s installation, operation, and maintenance manuals for
proper installation procedures.
na2271a
Condensate drain line
Warning: To prevent
equipment damage from
condensate, do not leave the
condensate drain line coiled
inside the equipment. Route
the condensate drain line out
the top or bottom of the
equipment. See “Condensate
pump drain installation” on
this page.
Note: Sufficient PVC drain line
is supplied to route the drain to
the outside of the equipment. To
route the drain line to a remote
drain, obtain additional
hardware.
na1576a
Top routing
Bottom routing
Note: Comply with all local codes when installing the
condensate drain line to the proper drain system.
Warning:
Failure to properly route the condensate
drain line before operation could result in water
damage.