InRow Half-Rack RC Installation32
Specifications
Note: For additional capacity and performance data, consult the InRow RC Technical Data
Manual.
Electrical
Input voltage 100-240 V; 50/60 Hz; 1 Ph
Rated current 10.1 A at 100 V
9.2 A at 120 V
5.1 A at 208 V
4.6 A at 230 V
4.4 A at 240 V
Condensate pump 5 l/h (1.3 GPH), 4.9-m (16-ft) vertical rise, 15-m (50-ft)
horizontal run
Physical
Physical dimensions
W x D x H
300 x 1068.9 x 1991.1 mm
(11.80 x 42.08 x 78.39 in)
Net weight (InRow RC only) 162.77 kg (358.5 lb)
Shipping weight
Single
Double
192.77 kg (425.0 lb)
355.62 kg (784.0 lb)
Environmental
Cooling capacity
18.2 kW (62,000 BTU/hour) total at 29.4°C (85°F)/31%
humidity and 7.2ºC (45ºF) entering chilled water
Airflow–high 76.45 m
3
/minute (2900 CFM)
Sound pressure 75 dBA at2700SCFM and 1.0 m in front of equipment (ref
20 μPa)
78.5 dBA at 2,900 SCFM and 1.0 m in front of equipment
(ref 20 μPa)
Entering air (maximum) 41ºC (105ºF)
Entering water 7.22°C at 45 l/m (45°F at 13.0 GPM)
Exiting water 12.77°C at pressure drop = 50 kPa (55°F at pressure drop =
17ft-H
2
O)
Recommended coolant requirements
Entering water temperature 7.2°C–12.7ºC (45°F–55ºF)
Flow rate (maximum) 77.6 l/m (20.5 GPM)
Water-side pressure drop 5.18 m-H
2
O at 49.21 l/m (17 ft-H
2
O at 13 GPM)
Maximum operating pressure 2068 kPa (300 psig) for hard-piped installations
1034 kPa (150 psig) for PEX installations
Comentarios a estos manuales