Troubleshooting: Semi-Annual Preventive Maintenance
44 InfraStruXure InRow RC—Operation and Maintenance
Water carryover • Improper fan speed selected • Select the next highest fan speed setting. For
example, change the fan speed setting from Low
to Med/Low.
Inlet water temperature is too
low
• Verify that the temperature of the inlet water is
within the specified range.
• Room humidity is too high • Adjust setpoint on dehumidifying equipment.
• Add additional dehumidifying equipment.
• Dirty coil • Clean the coil.
• Dirty filter • Clean the air filter.
••
••
Cooling unit sound
is higher than
expected
• Improper fan speed selected • Select a lower fan speed.
• Incorrect placement of
remote temperature sensor
• Verify that the remote temperature sensor is
properly located in the cold aisle.
Temperature control
not tight enough
• Improper placement of
remote temperature sensor
• Verify that the remote temperature sensor is
properly located in the cold aisle.
• Improper PID tuning • APC Worldwide Customer Support at a number
on the back cover of this manual.
Water on outside of
cooling unit
• Condensate drain hose is not
connected and/or not
properly routed outside the
Cooling Unit
• Verify that the condensate drain hose is properly
connected to the pump and properly routed
outside of the cooling unit.
• Verify that the condensate drain line does not
exceed 12 feet lift and 30 feet horizontal run.
• Leak in piping system • Locate and repair the leak.
• cooling unit not leveled
properly
• Adjust the leveling feet of the cooling unit.
• Damaged piping insulation • Identify damaged area and repair the insulation.
Water valve not
responsive
• Actuator not connected
properly
• Verify that the actuator is connected properly.
• Actuator and shaft not
rotating together
• Tighten the linkage screw on the actuator shaft.
• Rotary switch on the bottom
of the actuator is set
incorrectly
• Confirm that the rotary switch is pointing toward
the front of the cooling unit.
Display interface
not operational but
cooling unit
operates
• Display interface not
connected properly
Verify that the display interface cable is connected
properly.
Problem Possible Cause Corrective Action