23InRow RP CW Installation
Mechanical Connections
Top water piping
Note: The top chilled water supply pipe is supplied with the equipment and must be installed
on-site.
Note: You may need to remove the top panel from the equipment to gain access to the water
connections.
Note: New items are provided with the equipment as shown. See “Install kit inventory” on
page 5.
1. Remove the air filters.
2. Loosen the two screws holding the rear
condensate drain pan bracket
and remove the
bracket.
3. Loosen the two screws holding the air filter
bracket
located on the left side of the unit and
remove the bracket.
4. Remove the insulation cap from the union (not
shown).
5. From both supply and return connections,
remove the union nuts
and save for reuse.
Remove and discard the union end blank plates
and the gaskets
.
6. Position the insulated chilled water supply pipe
in the equipment. Mount a new gasket
and
connect the pipe to the union. Tighten the union
to 20 Nm (14.8 ft-lb).
7. Insulate the joint with the
provided insulation (not shown).
8. Connect the water supply pipe
to the field-installed pipe
using
a gasket
, union end
, and
union nut
.
9. Connect the cold water return
fitting to the field-installed pipe
using two gaskets
, union
end
, union nut
and
extension adapter
.
10.Reinstall the air filter bracket
.
11. Reinstall the rear condensate
drain pan bracket
and the air
filters.
12.Reinstall the top panel, if
removed.
na2027a
na2576a