InRow RP CW Installation24
Bottom water piping
1. Remove the insulation cap from the
union
(not shown).
2. Remove the union nut
, and save it for
reuse. Remove and discard the union
end blank plate
, and the ring seal
.
3. Install the union nuts
to field-
supplied tubing
.
4. Install new ring seals
, extension
adapters
, and insertion adapters
,
as shown.
na2745a
Note: New items are
provided with the equipment
as shown. See “Install kit
inventory” on page 5.