InRow RD Operation and Maintenance28
Network Configuration
The cooling unit is shipped with a Network Management Card (NMC) that enables you to manage the
cooling unit over your network. Configure the network settings for the equipment Network Management
Card from the display interface. The management card allows remote control and configuration of the
equipment.
Configure the network
Path: Main > Configure Network
MAC Address.
Displays the unique network identifier assigned to the Network Management Card of
the cooling unit installed in the cooling unit at the factory.
Boot Mode. Set the method by which the Network Management Card of the cooling unit will acquire its
network settings.
• Manual: Enter the IP Address, subnet mask, and default gateway using the IP Address menu.
• BOOTP: Set the Network Management Card of the cooling unit to obtain its network settings
from a BOOTP server.
• DHCP: Set the Network Management Card of the cooling unit to obtain its network settings from
a DHCP server.
• BOOTPDHCP: Set the Network Management Card of the cooling unit to search for its network
settings from either a BOOTP or a DHCP server.
By default, DHCP requires an APC cookie before it will accept an IP address. See
“DHCP” on page 36 for more information.
IP Address. You will be prompted to enter an Admin password. Enter the password and press ENTER to
return to the IP screen. Press
ENTER again to change the following settings for Manual boot mode only.
• IP: Enter the IP address assigned to the Network Management Card of the cooling unit.
• SM: Enter the subnet mask for the Network Management Card of the cooling unit.
• GW: Enter the default gateway for the Network Management Card of the cooling unit.