33User Guide InfraStruxure 150kVA Power Distribution Unit
sysOutput
Access: Administrator, Device
Description: View each phase-to-phase voltage, each phase-to-neutral voltage, load supported by each
phase and the frequency. Output measurements are made at the transformer.
Example:
apc> sysOutput
1. L1-L2,0V,L2-L3,0V,L3-L1,0V
2. L1,119V,19.4A,2.4kW,1.0,L2,119V,22.9A,2.7kW,1.0,L3,118V,21.1A,2.6kW,1.0
3. 60.0Hz
sysAlrmCfg
Access: Administrator, Device
Description: View the configuration of the system alarm thresholds.
Display order:
Maximum output voltage threshold and enable
High output voltage threshold and enable
Low output voltage threshold and enable
Minimum output voltage threshold and enable
Maximum current threshold and enable
High current threshold and enable
Low current threshold and enable
Minimum current threshold and enable
Frequency Deviation enable
Example:
apc> sysAlrmCfg
1. MaxV,+20%,Disable,HiV,+12%,Disable,LoV,-12%,Disable,MinV,-20%,Disable
2. MaxA,0%,Disable,HiA,0%,Disable,LoA,0%,Disable,MinA,0%,Disable,Freq,
Disable