39User Guide InfraStruxure 150kVA Power Distribution Unit
subfdThrMx
Access: Administrator, Device
Description: Configure the maximum load alarm threshold and critical alarm for target subfeed.
Parameters: [[<thresh>] [ <enable|disable>]]
Thresh = % rated load
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,90%,Disable,70%,Disable,20%,Disable,10%,Disable
apc> subfdThrMx 95 enable
1. Disable,Enable,95%,Enable,70%,Disable,20%,Disable,10%,Disable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,70%,Disable,20%,Disable,10%,Disable
subfdThrHi
Access: Administrator, Device
Description: Configure the high load alarm threshold and warning alarm for the target subfeed.
Parameters: [[<thresh>] [ <enable|disable>]]
Thresh = % rated load
Example:
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,70%,Disable,20%,Disable,10%,Disable
apc> subfdThrHi 75 enable
1. Disable,Enable,95%,Enable,75%,Enable,20%,Disable,10%,Disable
apc> subfdStatus 1
1. Normal,Open,160A,765kWh,10/27/2012
2. Disable,Enable,95%,Enable,75%,Enable,20%,Disable,10%,Disable