APC PDPB150G6F Guía de usuario Pagina 63

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 116
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 62
55User Guide InfraStruxure 150kVA Power Distribution Unit
icAlarm
Access: Administrator, Device
Description: Enable/disable alarm of the targeted input contact.
Parameters: <alarm>
alarm = enable|disable
Example:
apc> icStatus
1. New Contact 1,Critical,Critical,Open,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4
apc> icAlarm disable //disabling clears the alarm
1. New Contact 1,Normal,Critical,Closed,Door Switch
apc> icStatus
1. New Contact 1,Normal,Critical,Closed,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4
icSeverity
Access: Administrator, Device
Description: Enable/disable alarm of the targeted input contact.
Parameters: <severity>
alarm = critical|warning
Example:
apc> icStatus
1. New Contact 1,Critical,Critical,Open,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4
apc> icSeverity warning
1. New Contact 1,Normal,Warning,Closed,Door Switch
apc> icStatus
1. New Contact 1,Normal,Warning,Closed,Door Switch
2. User Contact 2,Normal,Warning,Open,Location 2
3. User Contact 3,Normal,Warning,Open,Location 3
4. User Contact 4,Normal,Critical,Open,Location 4
Vista de pagina 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 115 116

Comentarios a estos manuales

Sin comentarios