APC Switched Rack Power Distribution Unit (PDU) Guía de usuario Pagina 101

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 130
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 100
Metered-by-Outlet With Switching Rack PDU User Guide92
Administration: Notification
Event Actions
Path: Administration > Notification > Event Actions > options
Types of notification
You can configure event actions to occur in response to an event or group of events. These actions notify
users of the event in any of several ways:
Active, automatic notification. The specified users or monitoring devices are contacted directly.
E-mail notification
SNMP traps
– APC Remote Monitoring Service
Syslog notification
Indirect notification
Event log. If no direct notification is configured, users must check the log to determine which
events have occurred
You can also log system performance data to use for device monitoring. See “Data log” on
page 75 for information on how to configure and use this data logging option.
Queries (SNMP GETs)
For more information, see “SNMP” on page 88. SNMP enables an NMS to perform
informational queries. For SNMPv1, which does not encrypt data before transmission,
configuring the most restrictive SNMP access type (READ) enables informational queries
without the risk of allowing remote configuration changes.
Configure event actions
Notification parameters. For events that have an associated clearing event, you can also set the
following parameters as you configure events individually or by group, as described in the next two
sections. To access the parameters, click the receiver or recipient name.
Parameter Description
Delay x time before
sending
If the event persists for the specified time, a notification is sent. If the condition clears
before the time expires, no notification is sent.
Repeat at an interval
of x time
The notification is sent at the specified interval (e.g., every 2 minutes).
Up to x times During an active event, the notification repeats for this number of times.
Until condition
clears
The notification is sent repeatedly until the condition clears or is resolved.