APC Switched Rack Power Distribution Unit (PDU) Guía de usuario Pagina 49

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 130
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 48
Metered-by-Outlet With Switching Rack PDU User Guide40
olLowLoad
Access: Administrator, Device User
Description: Set or view the outlet low-load threshold in kilowatts. To specify an outlet, choose from
the following options.
Example 1: To set the low-load threshold for all outlets to 1 kW, type:
apc> olLowLoad all 1
E000: Success
Example 2: To view the low-load threshold for outlets 1 through 5, type:
apc> olLowLoad 1-5
E000: Success
1: 1 kW
2: 1 kW
3: 1 kW
4: 1 kW
5: 1 kW
Example 3: To view the low-load threshold for outlets 1 through 3 on guest Rack PDU 2, type:
apc> olLowLoad 2:1-3
E000: Success
1: Outlet 1: 0 W
2: Outlet 2: 0 W
3: Outlet 3: 0 W
olName
Access: Administrator, Device User, and Outlet User, but only for outlets to which the user is assigned.
Description: Set or view the name configured for an outlet.
Example 1: To configure the name for outlet 3 to BobbysServer, type:
apc> olName 3 BobbysServer
E000: Success
Example 2: To view the names of outlets 3 through 5 on guest Rack PDU 2, type:
apc> olName 2:3-5
E000: Success
3: BobbysServer
4: Outlet 4
5: Outlet 5
Argument Definition
all All device outlets.
<outlet#> A single number or a range of numbers separated with a dash, or a comma-
separated list of single outlet numbers and number ranges.
Argument Definition
all All device outlets.
<outlet#> A single number or a range of numbers separated with a dash, or a comma-
separated list of single outlet numbers and number ranges.
<newname> The name for a specific outlet. Use only letters and numbers.
Vista de pagina 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 129 130