InRoom CW/DX – Operating Instructions34
5. Transport/Storage
5.1 Delivery of units
The cooling units are mounted on pallets and packed several times wrapped in plastic fi lm. They must always
be transported upright on the pallets.
Note:
Units of the version A are delivered with 1 kg (2.2 lb) refrigerant charge.
Units of the version G contain the complete refrigerant charge.
Note:
When delivery is accepted, the unit is to be checked against the delivery note for comple-
teness and checked for external damage which is to be recorded on the consignment note
in the presence of the freight forwarder.
The delivery note can be found on the cooling unit when delivered.
• The shipment is made ex works, in case of shipment damages, please assert your claim
towards the carrier.
• Hidden damage is to be reported in writing within 6 days of delivery.
The following information can be found on the packing:
1) Logo
2) Order number
3) Typ e of unit
4) Packing piece - contents
5) Warning symbols
Also printed on the packing upon request:
6) Gross weight
7) Net weight
8) Dimensions
9) Customer order number
10) Additional customer requirements
Construction of protective covering
(from inside to outside)
1. Neopolene cushioning
2. Shrink fi lm
3. Additional board in container ship-
ments
5.2 Transport
The cooling units can be moved by lifting devices with ropes. The ropes have to be fi xed at the pallet, and
the upper unit edges have to be protected by wooden laths or metal brackets in such a way that they could
not be caved in.
Yo u can move the unit still packaged on the pallet with a forklift, if you take care that the center of gravity is
within the fork surface. Take care that the unit is in an upright position at the transport.
5.3 Storage
If you put the unit into intermediate storage before the installation, the following measures have to be carried
out to protect the unit from damage and corrosion:
• Make sure that the water connections are provided with protective hoods. If the intermediate storage
exceeds 2 months, we recommend fi lling the pipes with nitrogen.
The temperature at the storage point should not be higher than 42°C (107.6°F), and the site should not
be exposed to direct sunlight.
The unit should be stored packaged to avoid the risk of corrosion especially of the condenser fi ns.
Warning:
Never move the unit on rollers and never transport it without its pallet on a forklift, for the
risk of distorting the frame.