InRoom CW/DX – Operating Instructions
Kupferrohr Bogen Winkel T- Stück
Außen - Ø mm) 45° 90° 180° 90°
10 (3/8) 0,16 0,20 0,53 0,32 0,20
12 (1/2) 0,21 0,27 0,70 0,42 0,27
15 (5/8) 0,24 0,30 0,76 0,48 0,30
18 (3/4) 0,26 0,36 0,87 0,54 0,36
22 (7/8) 0,27 0,42 0,98 0,61 0,42
28 (1 1/8) 0,39 0,51 1,20 0,79 0,51
35 (1 3/8) 0,51 0,70 1,70 1,00 0,70
42 (1 5/8) 0,64 0,80 1,90 1,20 0,80
37
6.3.2.1 Selection of pressure and liquid line
- Establish the shortest route for pipework from the unit to the condenser. Make exceptions only tp
avoid unnecessary bends.
- Determine the required pipe fi ttings or specials between the unit and condenser.
- With the aid of table No. 1 on the bottom of this page, convert the pressure loss of the individual
fi t tings into equivalent pipe lengths, look up equivalent pipe lengths for pipe specials and fi ttings
and add these to the real pipe lengths.
- Select the pipe dimensions from diagram No. 1 on the following page corresponding to the calcu-
lated overall pipe length and refrigeration output.
Precautions for pressure line, if the condenser is higher than the unit.
- To ensure oil return in ascending hot gas lines, particularly at part load, the minimum refrigeration
capacity must not fall below the value stated on table 2 of the following page, for the corresponding
pipe size.
- For a refrigerant line set over 200 feet, contact factory for additional oil needed.
- Oil traps (even when an oil separator is installed) are to be installed every 5-6 m (16-20 ft) (sketch
3, page 40).
- The horizontal lines must always be routed with a slope towards the condenser.
Recommendation for liquid lines:
With liquid refrigerant, bubbles can form upstream of the expansion valve. This is always the case when
the ambient temperature is higher than the temperature of the liquid line (approx. +30°C (+86°F)) upstream
of the expansion valve. In this case insulation with Armafl ex or equivalent material with a wall thickness of
9 mm (0.4 in) is recommended for lines outside the unit. A thicker insulation is not required as the insulating
effect increases only insignifi cantly as the wall thickness increases.
Precautions for pressure lines:
Warning:
Pressure lines can reach a temperature of up to +80°C (+176°F) and should be insulated
inside the building at places where a possibility of contact exists.
Caution:
All work on refrigeration systems may only be carried out by qualifi ed APC approved per-
sonnel or by the customer service
Table 1: Pressure drop of pipe fi ttings or specials in meters for equivalent pipe length
Copper pipe Bend Angle T- piece
outside Ø
mm (in)
45° 90° 180° 90°
6.3.2 Refrigerant Piping