APC NetworkAIR CM Series: Optional Features 11
Remote shutdown. Events external to the unit, such as activation of a fire
suppression system may require the unit to shut down remotely. Additionally
this feature may be tied into a BMS that would allow remote control of the
units on/off status.
Remote relay shutdown. Remote shutdown of the NetworkAIR system
can be done by a factory installed relay. The relay can be ordered with a 24,
120, or 240 volt coil. The relay must be powered by others to disable the
NetworkAIR system.
Alarms/monitoring Custom alarm dry contact closures. Each unit can be equipped with any
or all of the listed dry contact closures. Upon activation of the associated
alarm, a discreet Normally-Open or Normally-Closed contact is available for
remote monitoring of that discreet alarm.
• High Temperature Alarm
• Low Temperature Alarm
• High Humidity Alarm
• Low Humidity Alarm
• Compressor High Pressure Alarm
• Fan Status Alarm
• Change Filter Alarm
• Fire Alarm (with addition of optional firestat)
• Smoke Detector Alarm (with addition of optional smoke detector)
• Humidifier Change Canister Alarm
• Water Underfloor Alarm (with addition of water detector)
Redundant group control. Allows up to six NetworkAIR units the ability
to communicate with each other to automatically switch upon alarm
condition, or timed rotation. Can also allow standby units the ability to assist
the running system.
Remote display panel. The microprocessor controller allows facility or
building-maintenance personnel to evaluate and control the unit from up to
50 ft. away from the unit, without having to enter the secured space.
Remote sensor(s). Environmental sensors can be strategically placed, up to
50 ft. from the unit to better meet the site’s cooling needs. The sensor must be
positioned to permit air movement across the sensors.
Disconnect, fused. A Nema 1 fused disconnected, complete with fuses, will
ship loose for field installation, thus allowing the disconnect to be unit-
mounted or remotely located on the following:
• Evaporator section/self-contained system.
• Remote indoor centrifugal type condenser/condensing unit.
Disconnect, non-fused. A Nema 1 disconnect with operating handle will be
factory installed on the following:
• Evaporator section/self-contained system.
• Remote indoor centrifugal type condenser/condensing unit.
A Nema 3R disconnect with operating handle will be shipped loose for field
installation on the remote, outdoor, propeller-type condenser/condensing unit