34 APC NetworkAIR CM Series: Guide Specifications
Smoke detector. A smoke detector shall ship loose for field installation into
ductwork. Upon smoke, the unit shall shut-down. If equipped with a
microprocessor, an audible and visual alarm shall be activated at the
microprocessor display/keypad.
Condensate pump. A condensate pump with a capacity of 36 GPH (37.8
mL/s) at 15 ft. (45 kPa) of head shall ship loose for field attachment to the
side of the unit. The condensate pump shall be complete with a 1.7qt. (1.6L)
reservoir, float switch, and pump/motor assembly.
Pre-cooling coil. The environmental control system shall be equipped with
a Pre-Cooling coil constructed of copper tubes/aluminum fins to serve as an
alternate source of cooling. pre-cooling shall be available when a pre-set
glycol temperature is available. If not available, the traditional DX cooling
mode will prevail. The pre-cooling coil shall have a total cooling capacity of
_____ MBH (_______ kW) and a sensible cooling capacity of _____ MBH
(_______ kW) based on an entering glycol temperature of _____° F (_____°
C) and leaving glycol temperature of _____° F (_____° C). The Pre-Cooling
coil shall require a flow rate of _______ GPM (_______ L/s) with a
maximum system pressure drop of _______ PSI (_______ kPa). The Pre-
cooling coil and water/glycol cooled condenser shall utilize the same inlet/
outlet connections.
ECWS cooling coil. The environmental control system shall be equipped
with an ECWS (External Chilled Water Supply) cooling coil constructed of
copper tubes/aluminum fins to serve as an alternate source of cooling. ECWS
cooling shall be available after verification of water flow and acceptable
water temperature. If not available, the traditional DX cooling mode will
prevail. The ECWS coil shall have a total cooling capacity of _______ MBH
(_______ kW) and a sensible cooling capacity of _______ MBH (_____ kW)
based on an entering water temperature of _______° F (_______° C) and
leaving glycol temperature of _______° F (_______° C). The ECWS coil
shall require a flow rate of _______ GPM (_______ L/s) with a maximum
system pressure drop of _______ PSI (_______ kPa). The ECWS coil and
water/glycol cooled condenser shall require separate inlet/outlet connections.