Management Card access problems
The following table describes problems that are related to network or other
access to the Management Card. If you are experiencing a problem that is
not described in this table, or in the table in SNMP issues, review the
troubleshooting flowcharts on the APC Network Management Card utility
CD (.\trouble\). If you still cannot resolve the problem, see Warranty and
Service.
Problem Solution
Unable to ping the Management
Card
Is the Management Card’s Status
LED green,
indicating it is up and running its
SNMP agent on the
network? If yes, try to ping another node on the
same network segment as the Management Card. If
that fails, it is not a Management Card problem. If
the Status
LED is not green, or if the ping test
succeeds, perform the following checks:
Verify that the Management Card is properly
seated in the
UPS or expansion chassis
Verify all network connections
Verify
IP addresses of the Management Card and
the
NMS, and make sure both are on the same
network or subnetwork
Verify the default gateway (or router)
IP address if
the
NMS is on a different physical network (or
subnetwork) from the Management Card
Verify the number of subnet bits for the
Management Card’s subnet mask