USER’S GUIDE
network management card
71
Turn UPS Off
Gracefully
1
Turns off power after two delays: a delay (Maximum Shutdown
Time plus two minutes) that allows time for PowerChute to
safely shut down its server, and the Shutdown Delay.
Reboot UPS
1
Reboots the attached equipment by doing the following:
• Turns off power at the
UPS after the Shutdown Delay
• Turns on power at the
UPS after the Return Delay
Reboot UPS
Gracefully
1
Reboots the attached equipment by doing the following:
• Turns off power after two delays: a delay (Maximum
Shutdown Time plus two minutes) that allows time for
PowerChute to safely shut down its server, and the
Shutdown Delay
• Turns on power after the Return Delay
Put UPS To Sleep
Puts the
UPS into its sleep mode (turns off power for a defined
period of time), as follows:
• Turns off power after the Shutdown Delay
• Turns on power after two delays: Sleep Time and Return
Delay
Put UPS To Sleep
Gracefully
1
Puts the UPS into its sleep mode (turns off power for a defined
period of time), as follows:
• Turns off power after two delays: a delay (Maximum
Shutdown Time plus two minutes) that allows time for
PowerChute to safely shut down its server, and the
Shutdown Delay
• Turns on power after two delays: Sleep Time and Return
Delay
Put UPS In/Take
UPS Off Bypass
Controls the use of the bypass, an operational mode that allows
maintenance to be performed at a Matrix-UPS or Symmetra
UPS without turning off power at that UPS.
Action Definition
1 The Web interface has a Signal servers option. When Yes is selected for that option,
initiating a Turn UPS Off, Reboot UPS, or Put UPS To Sleep action is equivalent to selecting
the Turn UPS Off Gracefully, Reboot UPS Gracefully, or Put UPS To Sleep Gracefully
options which are available in the control console.