APC Network Management Card AP9617 Guía de usuario Pagina 74

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 150
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 73
®
®®
®
USERS GUIDE
network management card
68
Smart-UPS, Matrix-UPS, or Symmetra UPS. You can use diagnostics
options to perform the following tests.
Symmetra 3-Phase UPS. The Diagnostics page in the Web interface
provides buttons you use to perform self-tests (Tests...) or runtime
calibrations (Calibrate...).
In the Web interface, the Diagnostics page reports the results of
the last self-test and last runtime calibration; In the control
console, you can use a Detailed Status (all Smart-UPS or
Matrix-UPS models) or Detailed
UPS Information (Symmetra or
Silcon UPS models) option to access these results
.
Test Definition
Self-Test Causes the
UPS to perform a self-test.
Simulate Power
Failure
Causes the
UPS to test its ability to go on battery.
Start/Stop Runtime
Calibration
Initiates (or cancels) a runtime calibration, a process which
determines how much runtime the
UPS has available when its
battery is at 100% capacity.
Note: Only perform a runtime calibration when the battery is at
100% capacity.
Test UPS Alarm
(Smart-UPS
or
Matrix-UPS)
Causes a Matrix-UPS to generate an alarm tone, and a
Smart-UPS to generate an alarm tone and flash its front panel
lights.
In the Web interface, the Diagnostics page reports the results of
the last self-test and last runtime calibration, as well as Intelligence
Modules, Power Modules, Batteries, and Communication Bus &
Subsystems status; in the control console, you can use the
Detailed UPS Information option to access this status information.
Vista de pagina 73
1 2 ... 69 70 71 72 73 74 75 76 77 78 79 ... 149 150

Comentarios a estos manuales

Sin comentarios