USERS GUIDE
network management card
15
How to Recover from a Lost Password
You can use a local computer, a computer that connects to the Management
Card through the serial port at the Management Cards UPS or expansion
chassis, to access the control console.
1. Select a serial port at the local computer and disable any service which
uses that port.
2. Unless an APC smart-signaling cable (940-0024 or 940-1524) is
already connected to the selected port, connect the smart-signaling
cable that came with the Management Card to the selected port and to
the serial port at the Management Cards UPS or chassis.
3. Run a terminal program (such as HyperTerminal) and configure the
selected port for 2400 bps, 8 data bits, no parity, 1 stop bit, and no flow
control, and save the changes.
4. Press
ENTER to display the User Name prompt.
5. Press the Reset button on the Network Management Card, which
causes the it to restart, a process that takes approximately 15 seconds.
6. Press
ENTER as many times as necessary to redisplay the User Name
prompt, then use apc for the user name and password. (If you take
longer than 30 seconds to log on after the User Name prompt is
redisplayed, you must start the login procedure again at step 4.)
7. From the Control Console menu, select System, then User Manager.
8. Select Administrator, and change the User Name and Password
settings, both of which are now defined as apc.
9. Press
CTRL-C and log off.
Reconnect any cable disconnected in step 2, and restart any
service disabled in step 1.