USER’S GUIDE
network management card
88
Control options for Silcon UPS. By default, no control options are
available for Silcon UPS.
To use control options for a Silcon UPS, you must enable the Accept
Remote Turn Off Commands option, available only in the control
console’s UPS Control menu and only when you use a local, serial
connection to access the control console.
When Accept Remote Turn Off Commands is enabled:
• Two control options, Turn UPS Off and Turn UPS Off Gracefully
options, become available for a Silcon UPS
• A Disable Remote Turn Off Commands option is available in the
UPS Control menu at the Web interface and control console, allowing
you to disable using the Management Card to turn off the Silcon UPS
To use a serial connection, see Local access to the control
console.