USERS GUIDE
network management card
86
Reboot UPS This option restarts the attached equipment by doing the following:
Turns off power at the UPS after the Shutdown Delay
Turns on power at the UPS after the UPS battery capacity returns to
at least the percentage configured for Return Battery Capacity and
the UPS waits the time specified as Return Delay.
For a Synchronized Control Group action:
This option turns off power at the UPSs that are enabled group
members after waiting the time configured as the initiating UPSs
Shutdown Delay
The initiating UPS then waits up to the number of seconds specified
as Power Synchronized Delay to allow time for group members to
regain input power. If all group members have already regained input
power, this delay is omitted. If all group members regain input power
during the delay, the remainder of the delay is cancelled.
The Return Delay then starts when the initiating UPS is at its
configured Return Battery Capacity.
The Return Battery Capacity of the initiating UPS is also required of
group members, but you can reduce the capacity required of a group
member by configuring that members Return Battery Capacity
Offset (set at 10% by default). For example, if the initiators Return
Battery Capacity is set at 50%, and a members Return Battery
Capacity Offset is set to 5%, that members battery capacity will
need to be at only 45% for that member to reboot.
Reboot UPS
Gracefully
1
(control
console)
This action is performed similarly to the Reboot UPS action, but with an
additional delay before the shutdown portion of the action. The attached
equipment shuts down only after the UPS (or the initiating UPS for a
Synchronized Control Group action) waits the Maximum Shutdown
Time plus two minutes. For information about how the Maximum
Shutdown Time is determined, see Maximum-Shutdown-Time
negotiation.
Action Definition
1 When you select Yes for the Web interfaces Signal servers option, initiating a Turn UPS
Off, Reboot UPS, or Put UPS To Sleep action is equivalent to selecting Turn UPS Off
Gracefully, Reboot UPS Gracefully, or Put UPS To Sleep Gracefully in the control
console.