USERS GUIDE
network management card
92
Shutdown Parameters
All of the following settings are available with Smart-UPS, Matrix-UPS,
Symmetra UPS, and Symmetra PX UPS models. A Silcon UPS uses only
the Low-Battery Duration, Maximum Shutdown Time, and Shutdown
Delay settings (under Shutdown Behavior Settings).
In the control console, use the Battery option in the
Configuration menu to access the Return Battery
Capacity setting.
Action Definition
Return Battery
Capacity
Defines the minimum battery capacity required before the UPS
turns on after a shutdown that was caused by a power failure.
N
OTE: The UPS must also wait the time defined by the Return
Delay setting before it can turn on.
Low-Battery
Duration
Defines how long the UPS can continue to run on battery power
after a low-battery condition occurs.
N
OTE: This setting also defines the time available for PowerChute
to safely shut down its server in response to the Control menu
options Turn UPS Off Gracefully, Reboot UPS Gracefully, and
Put UPS To Sleep Gracefully.
Maximum
Shutdown Time
(Web interface
only)
Reports the delay that is defined by the Maximum Shutdown
Time setting for the PowerChute Network Shutdown feature.
N
OTE: For information about the PowerChute Network Shutdown
feature, see PowerChute (UPS PowerChute Network Shutdown);
for information about how the Maximum Shutdown Time is
determined, see Maximum-Shutdown-Time negotiation.
Shutdown Delay Defines how long the UPS waits before it shuts down in response
to a turn-off command.