USER’S GUIDE
network management card
18
Main screen status fields.
• A Stat field reports the Management Card status.
Stat : P+ N+ A+
• A UPS model and name field reports the status of the UPS.
Smart-UPS 700 RM named Tester 8 : On Line
• The status of the probes (Thresholds) and contacts (Contact Alarms)
at any environmental monitor, including the Integrated Environmental
Monitor’s output relay (Relay) at an AP9618 or AP9619 Management
Card, is reported above the UPS status (UPS model and name) field.
Thresholds Ok, Contact Alarms Ok, Relay OK
P+ The APC operating system (AOS) is functioning properly.
N+ The network is functioning properly.
N? A BOOTP request cycle is in progress.
N– The Management Card failed to connect to the network.
N! Another device is using the Management Card’s IP address.
A+ The application is functioning properly.
A– The application has a bad checksum.
A? The application is initializing.
A! The application is not compatible with the AOS.
The AOS should always report that it is functioning properly
(P+); If the AOS is not functioning properly, and you can not
access the Management Card, see APC Worldwide Customer
Support to contact APC support staff.
For more information about the UPS status, see UPS Status;
for more information about probe, contact, and output relay
status, see Environment Menu.