Control
Initiating a UPS Control option
You can initiate a UPS Control option in either of these ways:
For the UPS of the initiating Management Card only.
In the Web interface, select No for Apply to Sync Group?
In the control console, type NO (in uppercase) in response to the
question Apply command to all SCG members?
For all members of the Synchronized Control Group to which this
Management Card belongs (if the option is allowed for Synchronized
Control Groups).
In the Web interface, select Yes for Apply to Sync Group?
In the control console, press
ENTER in response to the question
Apply command to all SCG members?
The following guidelines apply to Synchronized Control Groups:
All UPSs in a Synchronized Control Group must be the same model.
Synchronized Control Groups are supported for most UPS models of
the Smart-UPS and Symmetra UPS product lines. Any Smart-UPS or
Symmetra UPS with a card slot that accepts a Network Management
Card supports Synchronized Control Groups.
In a Synchronized Control Group of Symmetra 3-phase UPSs, the
shutdown mode setting must be either normal or secure for each UPS.
The option to apply an action to a Synchronized
Control Group is displayed only if this Management
Card is an active (enabled) member of a
Synchronized Control Group.
To configure a Management Card to be a member of a
Synchronized Control Group, see Sync Control.