USER’S GUIDE
network management card
82
Control
Initiating a UPS Control option
You can initiate a UPS Control option in either of these ways:
• For the UPS of the initiating Management Card only.
– In the Web interface, select No for Apply to Sync Group?
– In the control console, type NO (in uppercase) in response to the
question Apply command to all SCG members?
• For all members of the Synchronized Control Group to which this
Management Card belongs (if the option is allowed for Synchronized
Control Groups).
– In the Web interface, select Yes for Apply to Sync Group?
– In the control console, press
ENTER in response to the question
Apply command to all SCG members?
The following guidelines apply to Synchronized Control Groups:
• All UPSs in a Synchronized Control Group must be the same model.
• Synchronized Control Groups are supported for most UPS models of
the Smart-UPS and Symmetra UPS product lines. Any Smart-UPS or
Symmetra UPS with a card slot that accepts a Network Management
Card supports Synchronized Control Groups.
• In a Synchronized Control Group of Symmetra 3-phase UPSs, the
shutdown mode setting must be either normal or secure for each UPS.
The option to apply an action to a Synchronized
Control Group is displayed only if this Management
Card is an active (enabled) member of a
Synchronized Control Group.
To configure a Management Card to be a member of a
Synchronized Control Group, see Sync Control.