USER’S GUIDE
network management card
80
Smart-UPS, Matrix-UPS, or Symmetra UPS. You can use diagnostics
options to perform the following tests.
For the results of the last self-test and last runtime calibration:
• In the Web interface, use the “Diagnostics” page.
• In the control console, use the option Detailed Status
(Smart-UPS or Matrix-UPS models) or Detailed
UPS
Information (Symmetra or Silcon UPS models).
Test Definition
Self-Test Perform a self-test of the UPS.
Simulate Power
Failure
Causes the UPS to test its ability to switch to battery operation.
Start/Stop
Runtime
Calibration
Initiates (or cancels) a runtime calibration, a process which
calculates how much runtime the UPS has available.
N
OTE: You can perform a runtime calibration only when the battery is
at 100% capacity.
Test UPS Alarm
(Smart-UPS
or
Matrix-UPS)
Causes a Matrix-UPS to generate an alarm tone, and a Smart-UPS
to generate an alarm tone and flash its front panel lights.
If the Smart-UPS is a member of a Synchronized Control Group:
• In the Web interface, this option always tests the alarms of all
enabled members of the group.
• In the control console, you are prompted to choose whether to
apply the action to the initiating UPS or to all members of the
group.
• In SNMP, you can set the OID upsAdvControlFlashAndBeep to
either option: flashAndBeep (2) to test the alarm of an individual
UPS or flashAndBeepSyncGroup (3) to test the alarms of all
enabled group members.