A5
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display
Valves
G-valve
The pressure setpoint is entered in the 2nd
line and relates to the refrigerant condensa
-
tion pressure in the condenser.
➊
The pre-start serves to provide a sufficient
flow for the heat absorbing medium and to
pre-cool the heat absorbing medium. When
compressor operation is requested, the
G-valve opens and the compressor start is
delayed by the pre-start time. ➋
The pre-open value is the G-valve opening
which should be obtained during the pre-
start time.
➌
To avoid a constant discrepancy from the
set value there are three parameters, which
imitate the behavior of an integral control.
The control factor
➍ is the decisive value, by
which the extent of the control correction is
adjusted in the way of calculating the actua
-
ting variable after the lapse of an adjustable
control cycle ➎ (0-10 sec) according to the
following formula:
S
new
= S
old
- f • (set value - actual value)
S: actuating variable - in this case, valve
opening
f: control factor
Set value: condensation pressure
To avoid a drastical change you can adjust
a maximum control correction
➏ (0 - ±10%).
This control correction relates to the old
actuating variable in each cycle.
gvalve press 18.4
gvalve pretime 15
gvalve preopen 40
gvalve fact 2
gvalve concyc 5
gvalve maxc 5