61InRoom Controller - Operating Instructions
K7
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Cooling
Pumps
By setting the parameter "ACTIVE" on 1 you
add a pump to the configuration. With "0" you
disable the pump.
In the next line you determine which type the
pump shall belong to (1 = G-pump, which
pumps the medium through the condenser
in a GE2-unit, 2 = GE-pump, which pumps
the medium through the free cooling coil in
a GE2-unit, 3 = Glycol-pump - all pumps for
G-, GE1 units which are located outside the
cooling unit).
With the parameter "D-OUT" you determi-
ne a digital output for a glycol pump on/off
signal.
With the parameter "A-OUT" you adjust the
analogous output of the proportional signal
for a G/GE-pump.
The digital input for the pump alarm can be
assigned by the "D-IN" parameter.
The pump runtime can be set in the next
line.
For glycol pumps you can enable a sequen-
cing based on time and failure. With "partner
unit" and "partner pump" you select the
number of the 2nd pump and the ID of the
unit from which this pump is controlled.
pump 1 conf 1
pump 1 type 2
pump 1 dout 3
pump 1 aout 4
pump 1 alarm 3
pump 1 runtime 60
pump 1 partunit 17
pump 1 partpump 1