InRoom Controller - Operating Instructions68
R2
Service
The corresponding commands:
Display
T/H sensor for
return air
Return air
Supply air
T/H sensor for supply air
T/H sensor for
room air
Height > 1.5 m
Gen. settings
Control
Here you can choose the control type.
The display of the actual values changes
corresponding to the above adjusted type
of control (Room / Sup.Air).
The room air control is the standard con-
trol. The temperature/humidity sensor is
placed in the return air intake and the
InRoom Controller controls in accordance
with the setpoints set in the "Control/tem-
perature/humidity" menu. The limit values
of room air are monitored.
An external T/H sensor is required for
supply air control. The control takes place
for the room air control in accordance with
setpoints for the supply air set in the "Con
-
trol/temperature/humidity" menu. The limit
values of the supply air are monitored.
The sensor should be positioned de
-
pending on the room conditions, the
thermal load distribution in the room
and selected type of control.
The maximum distance to the IOC
can be 20m.
Four different control types can be
chosen by entering the corresponding
number:
1: room air
2: supply air
3: room air with supply air limitation
4: supply air with room air limitation
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
See next page for explanation of the com
-
mands - .
control 2
lim temp 16.3
grad temp 0.6
lim humi 75.0
grad humi 0.6