67InRoom Controller - Operating Instructions
P6
Service
The corresponding commands:
Display Equipment
Aux. Ports/Aux. Alarm
In the first line you can type in the alarm text
which you want to be displayed in case of
the alarm.
By setting the parameter "ACTIVE" on 1 you
add an external alarm to the configuration.
With "0" you disable the ext. alarm.
With the parameter "D-IN" you adjust the
digital input for the alarm signal.
You can adjust, whether the external alarm
releases a common alarm (0= no, 1 = yes).
Setting the priority for the external alarm
means assigning the alarm to an alarm relay
with the adjusted number.
The external alarm delay can be adjusted.
Times are entered in seconds.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
exalarmin 1 text xxx123
exalarmin 1 conf 1
exalarmin 1 alarm 11
exalarmin 1 commonalarm 0
exalarmin 1 alarmprio 9
exalarmin 1 alarmdelay 6