65InRoom Controller - Operating Instructions
➊
➋
➌
➍
➎
➏
➐
➑
➒
N6
Service
The corresponding commands:
Display Equipment
Sensor
Setting the parameter ACTIVE to 1 adds
a sensor to the configuration. Setting this
parameter to 0 disables the sensor. ➊
In the next line you determine the sensor
type (1: current, 2: voltage, 3: PT100,
4: PT1000, 5: KTY81-121).
➋
The parameter PURPOSE specifies for
what the sensor is used. ➌
See list at left.
With the parameter "A-IN" you adjust
the analogous input for the proportional
sensor signal.
➍
The following 5 items serve to calibrate
the sensor. The minimum measure value
(phys. value)
➎ is assigned to the mini-
mum output (value).
➐
The maximum measure value (phys. va-
lue) ➏ is assigned to the maximum output
(value).
➑
The unit of the adjusted measure value
depends on the sensor purpose (1-16).
The unit of the adjusted output depends
on the sensor type (1-5).
If there are more than two sensors with
the same purpose, an average value is
calculated. In the last line you can adjust
a maximum difference to the average
value.➒ If the maximum difference is
exceeded, the alarm "Sensor ## excess"
is released.
You need two water temperature sen
-
sors for:
1. GCW-units with dry coolers
Water temperature 1 is always the tem
-
perature for the CW-circuit.
Water temperature 2 is the cooling water
temperature, by which the dry coolers
are controlled.
2. CW2-units
Water temperature 1 is always the
temperature for the CW-valve which is
active, when no change-over has taken
place (no voltage at DIN 3).
Water temperature 2 is the temperature
for the second CW-valve, which is active
after a change-over.
PURPOSE:
1 - Room temperature
2 - Room humidity
3 - Supply temperature
4 - Supply humidity
5 - Water temperature 1
6 - Outside temperature
7 - Outside humidity
8 - Condensation temperature 1
9 - Condensation pressure 1
10 - Evaporation temperature 1
11 - Evaporation pressure 1
12 - Water temperature 2
13 - Condensation temperature 2
14 - Condensation pressure 2
15 - Evaporation temperature 2
16 - Evaporation pressure 2
17 - Setpoint temperature
18 - Setpoint humidity
Sensors of the purpose 8, 10, 11,
13, 15, 16 are not used up to now.
For these sensors and for the
sensor condensation pressure (9
and 14) no average value is cal
-
culated.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
sensor 1 conf 1
sensor 1 type 3
sensor 1 use 5
sensor 1 ain 3
sensor 1 minmeas -20.0
sensor 1 maxmeas 40.0
sensor 1 minout 0.0
sensor 1 maxout 9.0
sensor 1 div 20