97InRoom Controller - Operating Instructions
9. Network Management Card
9.1 Quick Configuration
The InRoom Precision Air Conditioner is shipped with a Network Management Card that enables you to manage
the air conditioner over your network. You must set up the Network Management Card to control the InRoom Pre-
cision Air Conditioner through a network.
The Network Management Card comes pre-assembled to an interface board using two sets of pin connections.
The interface board then connects to the controller board of the InRoom Precision Air Conditioner using a DB-15
connection, and a network connection is made by inserting an RJ-45 cable in to the ethernet port on the interface
board. The Network Management Card can be configured via a serial cable connected to the service port of the
controller board by using the nmcservice command.
Overview
You must configure the following TCP/IP settings before the InRoom Precision Air Conditioner can operate on a
network:
IP address of the Network Management Card
Subnet mask
Default gateway
Note: Never use the loopback address (127.0.0.1) as the default gateway address for the
Network Management Card. Doing so will disable the card and will require you to reset TCP/IP
settings to their defaults using a local serial login.
If a default gateway is unavailable, use the IP address of a computer that is located on the same
subnet as the Network Management Card and that is usually running. The Network Management
Card uses the default gateway to test the network when traffic is very light.
See “Watchdog Features” online at www.apc.com for more information about the watchdog
role of the default gateway.
TCP/IP configuration methods
Use one of the following methods to define the TCP/IP settings needed by the Network Management Card:
APC Device IP Configuration Wizard (See “APC Device IP Configuration Wizard” on page 98.)
BOOTP or DHCP server (See “BOOTP and DHCP configuration” on page 98.)
Networked computer (See “Remote access to the control console” on page 100.)