InRoom Controller - Operating Instructions62
➊
➋
➌
➎
➏
➊
➋
➌
➍
➊
➋
N1
N2
N3
Service
The corresponding commands:
Times are entered in hours.
The numbered callouts refer to the corres
-
ponding passages in the descriptive text.
Display Heating
E-heating/Hotgas reheat/Hot
water reheat
Setting the parameter ACTIVE to 1 adds
a reheat to the configuration. Setting this
parameter to 0 disables the reheat.
➊
In the next line you determine the reheat
type (1: reheat with on/off control, 2: reheat
with proportional control).
➋
With the parameter "D-OUT" you determine
a digital output for the reheat. As the propor
-
tional electric reheat is controlled by pulse
width modulation, the reheat receives the
control signal by the digital output.
➌
The digital input for the electric reheat alarm
can be assigned by the "D-IN" parameter.
➎
The electric reheat runtime can be set in
the last line.
➏
With the parameter "A-OUT" you adjust the
analogous output of the proportional signal
for the pww-valve of a pww-reheat.
➍
eheat 1 conf 1
eheat 1 type 1
eheat 1 dout 3
eheat 1 alarm 7
eheat 1 runtime 0
pwwheat 1 conf 2
pwwheat 1 type 1
pwwheat 1 dout 5
pwwheat 1 aout 8
gasheat 1 conf 1
gasheat 1 dout 10