43InRoom Controller - Operating Instructions
a
a
b
c
T/°C
T/°C
A7
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display
Cooling
Pump
Depending on which pump type you have
configured, different parameters are decisive.
(See table 1).
The start temperature for the pump is entered
as a positive difference to the room tempe
-
rature setpoint.
The corresponding hysteresis for the pump
stop is only valid for pumps with on/off-control
such as the glycol pump.
For speed controlled pumps you can adjust
a gradient, which determines the range in
which the pump speed increases from 0 to
100%.
You can determine, whether the pump alarm
releases a common alarm (0= no, 1 = yes).
The pump alarm delay can be adjusted in
seconds.
Setting the priority for the pump alarm
means assigning the corresponding alarm to
an alarm relay with the adjusted number.
The pressure setpoint is entered in the 1st
line and relates to the refrigerant condensa
-
tion pressure in the condenser.
The pump pre-start serves to pre-cool the
heat absorbing medium. When compressor
operation is requested, the G-pump starts
and the compressor start is delayed by the
pump pre-start time.
The pre-speed is the G-pump speed which
should be obtained during the pre-start
time.
Table 1
Pump type G (1) GE (2) Glycol (3)
Start temp.
Hysteresis
Gradient
Press. setpoint
Pre-start
Pre-speed
GE-pump
Pump
speed
100%
0%
setpoint
Glycol-pump
Pump
ON
OFF
setpoint
The control factor a is the decisive
value, by which the extent of the control
correction is adjusted in the way of calcu
-
lating the actuating variable after the lapse
of an adjustable control cycle b (0-10
sec) according to the following formula:
S
new
= S
old
- f • (set value - actual value)
S: actuating variable - in this case pump
speed
f: control factor
Set value: condensation pressure
To avoid a drastical change you can ad
-
just a maximum control correction
c (0
- ±10%). This control correction relates to
the old actuating variable in each cycle.
pump 1 start 0.1
pump 1 hys 0.7
pump 1 grad 0.6
pump 1 commonalarm 0
pump 1 alarmdelay 6
pump 1 alarmprio 3
pump 1 press 18.4
pump 1 speed 96
pump 1 pretime 5
pump 1 prespeed 60
pump 1 fact 2
pump 1 concyc 5
pump 1 maxc 5