InRoom Controller - Operating Instructions80
U2-U5
T3-T5
U6-U7
Service
Display
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Manual Operation
The manual operation menu consists of
two columns of parameters which are
needed for the operation.
In the first column (titled EN.) you enable
the manual operation of the listed compo
-
nent by setting the parameter to "1".
The second column (titled STATE) dis-
plays the actual state of the component.
After you have enabled the manual ope
-
ration in the first column, you can switch
on/off the component itself.
For proportionally controlled components
you can enter a percentage in the second
column (titled VALUE) which corresponds
to an opening degree for a valve or a ca
-
pacity for any other component.
Components which exist either with on/off
control or with proportional control have
both columns (STATE and VALUE). But
only the corresponding parameter can
be changed.
Sensors and external alarms can be simu
-
lated by the manual operation for the pur
-
pose of testing the controller function.
When the manual operation menu is left
(e.g. when the main menu of the service
level is reached again), the manual opera
-
tion of each component is disabled and the
controller takes over the control again.
Instead of 0/1 for "off/on" you can enter
a percentage from 0 to 100 if the compo
-
nent is proportionally controlled.
When the fan is switched off, any other
component is electrically blocked and
can not be started.
The corresponding commands:
comp 1 hand 1
comp 1 handon 0
sensor 1 handon 25
sensor 1 hand 1