45InRoom Controller - Operating Instructions
E4
a
a
a
b
b
b
Control
The corresponding commands:
Times are entered in seconds.
The numbered callouts refer to the corres-
ponding passages in the descriptive text.
Display Humidification
Humidifier
Depending on which humidifier type you
have, different parameters are decisive.
The start humidity for every humidifier is
entered as a negative difference to the room
humidity setpoint.
The hysteresis for the humidifier stop is only
valid for humidifiers with on/off-control.
For proportional humidifiers you can adjust
a gradient, which determines the humidity
range in which the humidifying capacity
increases from 0 to 100%.
You can determine, whether the humidifier
alarm releases a common alarm (0 = no,
1 = yes).
The humidifier alarm delay can be adjusted
in seconds.
Setting the priority for the humidifier alarm
means assigning the corresponding alarm to
an alarm relay with the adjusted number.
In the following window you can adjust the
three parameters: common alarm
a b,
alarm delay a b and alarm priority a
b for the conductivity alarm at 5µS and
at 20µS.
These alarma are available with the applica
-
tion of a conductivity measuring instrument,
which is required to control the water con-
ductivity for Ultrasonic humidifiers.
On/Off-control
(type 1)
Humidifier
ON
OFF
Proportional (type 2)
Humidifier
100%
0%
setpoint
setpoint
%r.h.
%r.h.
humi 1 start 7.3
humi 1 hys 9.0
humi 1 grad 10.0
humi 1 commonalarm 1
humi 1 alarmdelay 6
humi 1 alarmprio 5
humi 1 commonalarm5 1
humi 1 alarmdelay5 6
humi 1 alarmprio5 5
humi 1 commonalarm20 1
humi 1 alarmdelay20 6
humi 1 alarmprio20 5